control de disparo y de cierre

Spanish to English Tech/Engineering Energy / Power Generation
These are the specifications for a public bid on 115 kV switches for a substation.

Para la S/E XYZ
Los interruptores deberán ser adecuados para operar en sistemas que tengan las siguientes características:
-El voltaje para el ***control de disparo y de cierre*** será de 125 voltios corriente directa.

Proposed translations

+3
1 hr
Selected

trip and close voltage

diaparo, in the context of circuit breakers, refers to the opening of the contacts when a fault occurs; cierre refers to the closing of the contacts to restore power to the supplied circuit. The source text is saying that both these operations require 125 Vdc commands.

Vacuum contactor retrofit of a low-voltage power circuit breaker ... - [ Traducir esta página ]
de JD Fischer - 1995
simultaneous "trip" and "close" commands result in the contactor remaining open. ... The low-voltage power circuit breakers are regulated by the ...
ieeexplore.ieee.org/iel3/3967/11454/00527003.pdf[PDF] Design and Fabrication of Low-Voltage Metal-Enclosed AC Power ... - [ Traducir esta página ]
Formato de archivo: PDF/Adobe Acrobat - Vista rápida
4.2.1 Low-voltage power circuit breakers shall be air break type and shall be ..... relays, and breaker trip and close circuits ...
www.pip.org/downloads/Sample-ELSSG01.pdf - SimilaresElectric Power & Transmission & Distribution - Medium Voltage ... - [ Traducir esta página ]
3 entradas - 3 autores
What you have is just what is in the breaker, there will be a fair amount of additional control circuitry that determines when the trip and close circuits ...
www.eng-tips.com/viewthread.cfm?qid=228059&page... - En cachéObtener más resultados de debate
[DOC] Balanced Dashboards - [ Traducir esta página ]
Formato de archivo: Microsoft Word - Versión en HTML
Sample Specification for Medium Voltage Replacement Breakers - General ... Manual trip and close handles shall be identified as “trip” and “close. ...
www.energy.siemens.com/...voltage...voltage...breakers/.../... - Estados Unidos
Peer comment(s):

agree slothm
40 mins
agree Richard Boulter
1 hr
agree Juan Vilca
3 hrs
Something went wrong...
4 KudoZ points awarded for this answer. Comment: "thank you very much!"
8 mins

triggering and making control voltage

"cierre" (de contactos) se traduce como "contact making"

Y por cierto: En español es "tensión", no "voltaje" y, desde luego, NADA de "corriente directa". Es "corriente continua"